Before starting the system,
switch on the liquid pump of N-PENTANE to build some pressure. Leave
it in Force mode after the start and put back the
pump in Auto mode. Don’t forget to switch on the
liquefier in Manual mode and leave it manual.
Disable flowcell alarm (Line 9 in RECIPE CONSTANT
of Distribution module). When flowcells in/out have reasonable
values, enable the alarm.
RPC
Before the system cab be restarted
the high pressure buffer must be filled at least up to 500 mbar
CMS
N2
Supply Alarm
The SMS message "Bad – CMSAUX_En_PSL004"
from CMS means that the N2 batteries are in use,
instead of the dewars.
You can check the
pressure in the batteries in this link.
Explanation/Screenshot of the Gas Supply Status
Page >
(.pdf)